Theoretical and experimental evaluation of a refrigeration compressor operating under controlled conditions in a calorimetric chamber

Authors

  • Ivoni Carlos Acunha Junior Instituto Federal de Educação, Ciência e Tecnologia (IFRS)
  • Stephanie dos Santos Pohlmann Instituto Federal de Educação, Ciência e Tecnologia (IFRS)
  • Lissandra Silveira da Silveira Instituto Federal de Educação, Ciência e Tecnologia (IFRS)
  • Marco Aurélio dos Santos Rahn Instituto Federal de Educação, Ciência e Tecnologia (IFRS)
  • Anderson Favero Porte Instituto Federal de Educação, Ciência e Tecnologia (IFRS)
  • Elizaldo Domingues dos Santos Universidade Federal do Rio Grande Programa de Pós-Graduação em Modelagem Computacional
  • Liércio André Isoldi Universidade Federal do Rio Grande Programa de Pós-Graduação em Modelagem Computacional
  • Michel Kepes Rodrigues Universidade Federal do Rio Grande Programa de Pós-Graduação em Modelagem Computacional

DOI:

https://doi.org/10.14808/sci.plena.2015.081329

Keywords:

Refrigeration hidrocarbonestos, compressors, computer simulation.

Abstract

The use of compressors with a variable frequency drive has been an alternative to reduce energy in refrigeration. In this work, we evaluated some performance parameters of a refrigeration compressor working with electric motor drive frequencies under 50 Hz and 60 Hz, using the refrigerant R-404a. Thus, measurements at a constant temperature of 32.2 °C were subjected held in an calorimeter chamber. The quantities measured were: temperature of dry and wet bulb calorimeter chamber, air velocity in the evaporator, the wet bulb temperature and relative humidity in the face area of the evaporator and insufflation, suction and discharge pressures of the compressor, voltage and electric current for the compressor motor. Capacity and power consumed by the electric motor of the compressor drive, which were used to determine the coefficient of performance and the isentropic compressor efficiency were measured. Furthermore, it was held mathematical modeling and computer simulation of the cooling capacity of the compressor, using both the performance data provided by the manufacturer, as those from the measurements. The results showed that the pattern obtained by the measurements has minor deviations in relation to the developed using data from the manufacturer to the conditions studied. Moreover, the best performers are achieved to drive with frequency of 60 Hz compared to 50 Hz.

Author Biography

Michel Kepes Rodrigues, Universidade Federal do Rio Grande Programa de Pós-Graduação em Modelagem Computacional

http://lattes.cnpq.br/0379919270609981

Published

2015-08-31

How to Cite

Junior, I. C. A., Pohlmann, S. dos S., da Silveira, L. S., Rahn, M. A. dos S., Porte, A. F., Santos, E. D. dos, Isoldi, L. A., & Rodrigues, M. K. (2015). Theoretical and experimental evaluation of a refrigeration compressor operating under controlled conditions in a calorimetric chamber. Scientia Plena, 11(8). https://doi.org/10.14808/sci.plena.2015.081329

Issue

Section

VI Conferência Sul em Modelagem Computacional

Most read articles by the same author(s)

1 2 3 > >>